14.9.5 Settings
PID-3906-SETTINGS v2
Table 439: LMBRFLO Group settings (basic)
Name
Values (Range) Unit Step Default Description
R1A 0.001 - 1500.000 Ohm/p 0.001 2.000 Source resistance A (near end)
X1A 0.001 - 1500.000 Ohm/p 0.001 12.000 Source reactance A (near end)
R1B 0.001 - 1500.000 Ohm/p 0.001 2.000 Source resistance B (far end)
X1B 0.001 - 1500.000 Ohm/p 0.001 12.000 Source reactance B (far end)
R1L 0.001 - 1500.000 Ohm/p 0.001 2.000 Positive sequence line resistance
X1L 0.001 - 1500.000 Ohm/p 0.001 12.500 Positive sequence line reactance
R0L 0.001 - 1500.000 Ohm/p 0.001 8.750 Zero sequence line resistance
X0L 0.001 - 1500.000 Ohm/p 0.001 50.000 Zero sequence line reactance
R0M 0.000 - 1500.000 Ohm/p 0.001 0.000 Zero sequence mutual resistance
X0M 0.000 - 1500.000 Ohm/p 0.001 0.000 Zero sequence mutual reactance
LineLengthUnit kilometer
miles
- - kilometer Line length unit
LineLength 0.0 - 10000.0 - 0.1 40.0 Length of line
Table 440: LMBRFLO Non group settings (basic)
Name
Values (Range) Unit Step Default Description
DrepChNoIL1 1 - 30 Ch 1 1 Recorder input number recording phase
current, IL1
DrepChNoIL2 1 - 30 Ch 1 2 Recorder input number recording phase
current, IL2
DrepChNoIL3 1 - 30 Ch 1 3 Recorder input number recording phase
current, IL3
DrepChNoIN 0 - 30 Ch 1 4 Recorder input number recording
residual current, IN
DrepChNoIP 0 - 30 Ch 1 0 Recorder input number recording 3I0 on
parallel line
DrepChNoUL1 1 - 30 Ch 1 5 Recorder input number recording phase
voltage, UL1
DrepChNoUL2 1 - 30 Ch 1 6 Recorder input number recording phase
voltage, UL2
DrepChNoUL3 1 - 30 Ch 1 7 Recorder input number recording phase
voltage, UL3
UL1Gain 0.000 - 10.000 - 0.001 1.000 Scale factor for fine tuning of voltage
magnitude L1
UL2Gain 0.000 - 10.000 - 0.001 1.000 Scale factor for fine tuning of voltage
magnitude L2
UL3Gain 0.000 - 10.000 - 0.001 1.000 Scale factor for fine tuning of voltage
magnitude L3
Section 14 1MRK 506 382-UEN A
Monitoring
624 Line distance protection REL650 2.2 IEC
Technical manual

Table of Contents

Other manuals for ABB REL650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REL650 and is the answer not in the manual?

ABB REL650 Specifications

General IconGeneral
BrandABB
ModelREL650
CategoryProtection Device
LanguageEnglish

Related product manuals