Name Type Description
NOEVENT BOOLEAN Event disabled during test mode
INPUT BOOLEAN IED TEST input is active
SETTING BOOLEAN IED test mode setting is On
IEC61850 BOOLEAN Active when LD0 Mode is in Blocked, Test or Test
blocked
19.3.4 Settings
IP11343-1 v2
PID-6730-SETTINGS v1
Table 607: TESTMODE Non group settings (basic)
Name Values (Range) Unit Step Default Description
IEDTestMode Off
On
- - Off Activate IED Test mode
EventDisable Off
On
- - Off Event disable during test mode
BlockAllFunc Off
On
- - On Block all functions when entering IED
test mode
CmdTestEd1 Off
On
- - Off Require test bit in command at test
mode (only for IEC61850 Ed1)
19.3.5 Operation principle
IP12116-1 v4
M12015-4 v10
Set the IED in test mode by
• configuration, activating the input SIGNAL on the function block
TESTMODE.
• setting TestMode to On in the local HMI, under Main menu/TEST/IED test
mode.
While the IED is in test mode, the output ACTIVE of the function block
TESTMODE is activated. The outputs of the function block TESTMODE shows
the cause of the “Test mode: being in On” state. If the input from the configuration
(OUTPUT signal is activated) or setting from local HMI (SETTING signal is
activated).
While the IED is in test mode, the yellow Start LED will flash and all functions can
be blocked depending on the configuration of the testmode component. Any
function can be unblocked individually regarding functionality and event
signalling.
M11828-3 v8
The deblocking is reseted when exiting test mode.
The blocking of a function concerns all output signals from the actual function, so
no outputs will be activated.