Name Values (Range) Unit Step Default Description
CTStarPoint10 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec10 1 - 10 A 1 1 Rated CT secondary current
CTprim10 1 - 99999 A 1 3000 Rated CT primary current
VTsec11 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim11 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec12 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim12 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
3.5 Monitored data
PID-6531-MONITOREDDATA v3
Table 13: AISVBAS Monitored data
Name Type Values (Range) Unit Description
Status INTEGER 0=Ok
1=Error
2=AngRefLow
3=Uncorrelated
-
Service value status
PID-3923-MONITOREDDATA v6
Table 14: TRM_7I_5U Monitored data
Name
Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok
1=Error
- Analogue input module
status
PID-3924-MONITOREDDATA v6
Table 15: TRM_9I_3U Monitored data
Name
Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok
1=Error
- Analogue input module
status
PID-6598-MONITOREDDATA v6
Table 16: TRM_10I_2U Monitored data
Name
Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok
1=Error
- Analogue input module
status
Section 3 1MRK 506 382-UEN A
Analog inputs
58 Line distance protection REL650 2.2 IEC
Technical manual

Table of Contents

Other manuals for ABB REL650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REL650 and is the answer not in the manual?

ABB REL650 Specifications

General IconGeneral
BrandABB
ModelREL650
CategoryProtection Device
LanguageEnglish

Related product manuals