PulseTime
Ondelay
OUTPUT 1
PulseTime
Ondelay
OUTPUT 2
PulseTime
Ondelay
OUTPUT 3
INPUT 17
I
N
P
U
T
3
2
INPUT 1
I
N
P
U
T
1
6
IEC09000612-3-en.vsd
³1
³1
³1
³1
&
&
&
&
&
&
³1
³1
t
t
t
Offdelay
t
t
t
t
Offdelay
t
Offdelay
t
ModeOutput1=Pulsed
ModeOutput2=Pulsed
ModeOutput3=Pulsed
IEC09000612 V3 EN-US
Figure 252: Trip matrix internal logic
Output signals from TMAGAPC are typically connected to other logic blocks or
directly to output contacts in the IED. When used for direct tripping of the circuit
breaker(s) the pulse time shall be set to at least 0.150 seconds in order to obtain
satisfactory minimum duration of the trip pulse to the circuit breaker trip coils.
13.3.7 Technical data
GUID-3AB1EE95-51BF-4CC4-99BD-F4ECDAACB75A v1
Table 285: Number of TMAGAPC instances
Function
Quantity with cycle time
3 ms 8 ms 100 ms
TMAGAPC 6 6 -
13.4 Logic for group alarm ALMCALH
GUID-64EA392C-950F-486C-8D96-6E7736B592BF v1
13.4.1 Identification
GUID-64EA392C-950F-486C-8D96-6E7736B592BF v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Logic for group alarm ALMCALH - -
Section 13 1MRK 506 382-UEN A
Logic
484 Line distance protection REL650 2.2 IEC
Technical manual

Table of Contents

Other manuals for ABB REL650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REL650 and is the answer not in the manual?

ABB REL650 Specifications

General IconGeneral
BrandABB
ModelREL650
CategoryProtection Device
LanguageEnglish

Related product manuals