11.4.8 Proxy for signals from switching device via GOOSE
XLNPROXY
11.4.8.1 Functionality
GUID-11F9CA1C-8E20-489B-822B-34DACC59553A v1
The proxy for signals from switching device via GOOSE (XLNPROXY) gives an
internal representation of the position status and control response for a switch
modelled in a breaker IED. This representation is identical to that of an SXCBR
function.
11.4.8.2 Function block
GUID-408513CD-A87E-45E8-8E44-24E153947F02 v1
XLNPROXY
BEH*
BEH_VALID*
LOC*
LOC_VALID*
BLKOPN*
BLKOPN_V*
BLKCLS*
BLKCLS_V*
POSVAL*
POSVAL_V*
OPCNT*
OP_CNT_V*
BLK
BLK_VAL
STSELD
STSELD_V
OPRCVD
OPRCVD_V
OPOK
OPOK_VAL
EEHEALTH
EEH_VAL
OPCAP
OPCAP_V
COMMVALID
XIN
XPOS
SELECTED
OP_BLKD
CL_BLKD
OPENPOS
CLOSEPOS
CNT_VAL
L_CAUSE
EEHEALTH
OPCAP
IEC16000043-1-en.vsdx
IEC16000043 V1 EN-US
Figure 208: XLNPROXY function block
11.4.8.3 Signals
PID-6712-INPUTSIGNALS v3
Table 226: XLNPROXY Input signals
Name
Type Default Description
BEH INTEGER -1 Behaviour
BEH_VLD BOOLEAN 0 Valid data on BEH input
LOC BOOLEAN 0 Local control behaviour
LOC_VLD BOOLEAN 0 Valid data on LOC input
BLKOPN BOOLEAN 0 Block opening
BLKOPN_VLD BOOLEAN 0 Valid data on BLKOPN input
BLKCLS BOOLEAN 0 Block closing
Table continues on next page
Section 11 1MRK 506 382-UEN A
Control
410 Line distance protection REL650 2.2 IEC
Technical manual

Table of Contents

Other manuals for ABB REL650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REL650 and is the answer not in the manual?

ABB REL650 Specifications

General IconGeneral
BrandABB
ModelREL650
CategoryProtection Device
LanguageEnglish

Related product manuals