Name Type Default Description
INPUT9 BOOLEAN 0 Binary input 9
INPUT10 BOOLEAN 0 Binary input 10
INPUT11 BOOLEAN 0 Binary input 11
INPUT12 BOOLEAN 0 Binary input 12
INPUT13 BOOLEAN 0 Binary input 13
INPUT14 BOOLEAN 0 Binary input 14
INPUT15 BOOLEAN 0 Binary input 15
INPUT16 BOOLEAN 0 Binary input 16
PID-4127-OUTPUTSIGNALS v3
Table 291: WRNCALH Output signals
Name Type Description
WARNING BOOLEAN OR function betweeen inputs 1 to 16
13.5.5 Settings
PID-4127-SETTINGS v3
Table 292: WRNCALH Group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
13.5.6 Operation principle
GUID-71C65C20-7B6C-499F-BFCD-E418AA55F7EC v2
The logic for group warning WRNCALH block is provided with 16 input signals
and 1 WARNING output signal. The function block incorporates internal logic OR
gate in order to provide grouping of connected input signals to the output
WARNING signal from the function block.
When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the
WARNING output signal will get logical value 1.
The function has a drop-off delay of 200 ms when all inputs are reset to provide a
steady signal.
WARNING
³1
200 ms
t
IEC13000192-1-en.vsd
INPUT1
INPUT16
IEC13000192 V1 EN-US
Section 13 1MRK 506 382-UEN A
Logic
488 Line distance protection REL650 2.2 IEC
Technical manual