4.1.3.1 Setting parameters for binary input modules
PID-3473-SETTINGS v2
Table 19: BIM Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - On Operation Off/On
DebounceTime 0.001 - 0.020 s 0.001 0.001 Debounce time for binary inputs
OscBlock 1 - 40 Hz 1 40 Oscillation block limit
OscRelease 1 - 30 Hz 1 30 Oscillation release limit
4.1.3.2 Setting parameters for binary input/output module
PID-4050-SETTINGS v2
Table 20: IOMIN Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - On Binary input/output module in operation
(On) or not (Off)
DebounceTime 0.001 - 0.020 s 0.001 0.001 Debounce time for binary inputs
OscBlock 1 - 40 Hz 1 40 Oscillation block limit
OscRelease 1 - 30 Hz 1 30 Oscillation release limit
Section 4 1MRK 506 382-UEN A
Binary input and output modules
62 Line distance protection REL650 2.2 IEC
Technical manual