310 Rockwell Automation Publication 750-IN001P-EN-P - April 2017
Chapter 5 I/O Wiring
Enclosure Options – Floor
Mount Frames 8…10
NEMA/UL Type 1 Enclosure – 2500 MCC Style Cabinet
The enclosure that is provided is a NEMA/UL Type 1 – 2500 MCC style
cabinet that is 600 mm or 800 mm deep (Position 6, Code B, L, P, or W). Type
1 enclosures are intended for indoor use primarily to provide a degree of
protection against limited amounts of falling dirt. Doors and openings are
sealed by a gasket. One of these options in the catalog number indicates
NEMA/UL Type 1 enclosures – 2500 MCC style cabinet:
• Position 6, Code B = 600 mm deep enclosure
• Position 6, Code L = 800 mm deep enclosure
• Position 6, Code P = 800 mm deep enclosure with MCC bus installed;
standard cabinet color (RAL 7032)
• Position 6, Code W = 800 mm deep enclosure with MCC bus installed;
Centerline 2100 gray color (ASA49)
NEMA Type 12 Enclosure – 2500 MCC Style Cabinet
The enclosure that is provided is a NEMA Type 12 – 2500 MCC style cabinet
that is 800 mm deep (Position 6, Code J, K, or Y). Type 12 enclosures are
intended for indoor use primarily to provide a degree of protection against
dust, falling dirt, and dripping noncorrosive liquids. One of these options in
the catalog number indicates NEMA Type 12 enclosure – 2500 MCC style
cabinet:
• Position 6, Code J = 800 mm deep enclosure
• Position 6, Code K = 800 mm deep enclosure with MCC bus installed;
standard cabinet color (RAL 7032)
• Position 6, Code Y = 800 mm deep enclosure with MCC bus installed;
Centerline 2100 gray color (ASA49)
Before performing any work on the drive, read the general precautions that
begin on page 15
.