Rockwell Automation Publication 1756-RM003N-EN-P - October 2011 171
Input/Output Instructions (MSG, GSV, SSV, IOT) Chapter 4
Block-Transfer Error Codes
These are the Logix5000 block-transfer specific error codes.
Error Code (Hex) Description Display In Software
00D0 The scanner did not receive a block-transfer response from the block-transfer module within 3.5
seconds of the request
Unknown error
00D1 The checksum from the read response did not match the checksum of the data stream
00D2 The scanner requested either a read or write but the block-transfer module responded with the
opposite
00D3 The scanner requested a length and the block-transfer module responded with a different length
00D6 The scanner received a response from the block-transfer module indicating the write request failed
00EA The scanner was not configured to communicate with the rack that would contain this block-transfer
module
00EB The logical slot specified is not available for the given rack size
00EC There is currently a block-transfer request in progress and a response is required before another
request can begin
00ED The size of the block-transfer request is not consistent with valid block-transfer size requests
00EE The type of block-transfer request is not consistent with the expected BT_READ or BT_WRITE
00EF The scanner was unable to find an available slot in the block-transfer table to accommodate the
block-transfer request
00F0 The scanner received a request to reset the remote I/O channels while there were outstanding block-
transfers
00F3 Queues for remote block-transfers are full
00F5 No communication channels are configured for the requested rack or slot
00F6 No communication channels are configured for remote I/O
00F7 The block-transfer timeout, set in the instruction, timed out before completion
00F8 Error in block-transfer protocol - unsolicited block-transfer
00F9 Block-transfer data was lost due to a bad communication channel
00FA The block-transfer module requested a different length than the associated block-transfer instruction
00FB The checksum of the block-transfer read data was wrong
00FC There was an invalid transfer of block-transfer write data between the adapter and the block-transfer
module
00FD The size of the block-transfer plus the size of the index in the block-transfer data table was greater
than the size of the block-transfer data table file