Rockwell Automation Publication 2080-UM002G-EN-E - March 2015 231
User Interrupts Appendix D
2. In the User Interrupt Configuration window, configure this POU as a User
Fault routine.
User Interrupt Instructions
STIS - Selectable Timed Start
STI0 is used in this document to define how STIS works.
Instruction Used To: Page
STIS – Selectable
Timed Start
Use the STIS (Selectable Timed Interrupt Start) instruction to
the start the STI timer from the control program, rather than
starting automatically.
231
UID – User Interrupt
Disable
Use the User Interrupt Disable (UID) and the User Interrupt
Enable (UIE) instructions to create zones in which user
interrupts cannot occur.
232
UIE – User Interrupt
Enable
234
UIF – User Interrupt
Flush
Use the UIF instruction to remove selected pending interrupts
from the system.
235
UIC – User Interrupt
Clear
Use this function to clear Interrupt Lost bit for the selected
User Interrupt(s).
236
STISSTIS
STIS(name or Pin ID)
or ENO(Pin ID)
Enable
IRQType
SetPoint