Rockwell Automation Publication 2080-UM002G-EN-E - March 2015 181
Specifications Appendix A
For the Micro850 relay chart, see Micro830 and Micro850 Relay Charts on
page 173.
Micro800 Programmable Controller External AC Power Supply
Certifications
Certification (when
product is marked)
(1)
Value
c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See
UL File E322657.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,
certified for U.S. and Canada. See UL File E334470.
CE European Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
European Union 2006/95/EC LVD, compliant with:
EN 61131-2; Programmable Controllers (Clause 11)
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
EtherNet/IP ODVA conformance tested to EtherNet/IP specifications.
KC Korean Registration of Broadcasting and Communications Equipment,
compliant with:
Article 58-2 of Radio Waves Act, Clause 3.
(1) See the Product Certification link at http://www.rockwellautomation.com/products/certification for Declaration
of Conformity, Certificates, and other certification details.
General Specifications
Attribute Value
Dimensions, HxWxD 90 x 45 x 80 mm (3.55 x 1.78 x 3.15 in.)
Shipping weight 0.34 kg (0.75 lb)
Supply voltage range
(1)
100V…120V AC, 1 A
200…240V AC, 0.5 A
Supply frequency 47…63 Hz
Supply power 24V DC, 1.6 A
Inrush current, max 24A @ 132V for 10 ms
40A @ 263V for 10 ms
Power consumption
(Output power)
38.4W @ 100V AC, 38.4W @ 240V AC
Power dissipation
(Input power)
45.1W @ 100V AC, 44.0W @ 240V AC
Isolation voltage 250V (continuous), Primary to Secondary: Reinforced Insulation Type
Type tested for 60s @ 2300V AC primary to secondary and 1480V AC
primary to earth ground.
Output ratings, max 24V DC, 1.6A, 38.4W