90 Rockwell Automation Publication 20A-UM001N-EN-P - July 2013
Appendix A Supplemental Drive Information
Table 14 - Specifications
TÜV TÜV Rheinland Certificate T72041027 01 tested to
EN 50178
XX
TÜV Rheinland Certificate of a Competent Body
AV 72061059 0001 for compliance with
EMC Directive (89/336/EEC)
X
TÜV Rheinland Certificate 968/EZ 166.01/06
Safe Off Option satisfies requirements for Category 3 safety function
according to EN 954-1
X
(1) See the product certifications website, http://www.rockwellautomation.com/products/certification/ for declarations of conformity,
certificates, and other certification details.
Category Specification
Protection Drive 200…
208V
240V 380/400 480V 600V 690V
AC input overvoltage trip 247V AC 285V AC 475V AC 570V AC 690V AC
AC input undervoltage trip 120V AC 138V AC 233V AC 280V AC 345V AC
Bus overvoltage trip 405V DC 405V DC 810VDC 810V DC 1013V DC
Bus undervoltage output shutoff 300V DC 300V DC 407V DC 407V DC 508V DC
Bus undervoltage fault level 160V DC 160V DC 300VDC 300V DC 375V DC
Nominal bus voltage 281V DC 324V DC 540VDC 648V DC 810V DC
All Drives
Heat sink thermistor Monitored by microprocessor overtemp trip
Drive overcurrent trip
Software current limit
Hardware current limit
Instantaneous current limit
20…160% of rated current
200% of rated current (typical)
220…300% of rated current (dependent on drive rating)
Line transients Up to 6000 volts peak per IEEE C62.41-1991
Control logic noise immunity Showering arc transients up to 1500V peak
Power ride-thru 15 milliseconds at full load
Logic control ride-thru 0.5 seconds minimum, 2 seconds typical
Ground fault trip Phase-to-ground on drive output
Short circuit trip Phase-to-phase on drive output
Environment
Altitude 1000 m (3300 ft) max without derating
Maximum surrounding air temperature
without derating
IP20, NEMA/UL Type 1
flange mount
IP66 NEMA/UL Type 4X/12
(for indoor use only)
0…50 °C (32…122 °F)
0…50 °C (32…122 °F)
0…40 °C (32…104 °F)
Cooling fan operation
Frames A and C
Frames B, D, and E
Fan operates when power is applied.
Fan operates when power is applied and in Run condition.
Storage temperature (all const.) –40…70 °C (–40…158 °F)
Atmosphere Important: Drive must not be installed in an area where the
ambient atmosphere contains volatile or corrosive gas, vapors, or
dust. If the drive is not going to be installed for a period of time,
store the drive where it is not exposed to a corrosive atmosphere.
Relative humidity 5…95% non-condensing
Shock 15 g peak for 11 ms duration (±1.0 ms)
Vibration 0.152 mm (0.006 in.) displacement, 1 g peak
Surrounding environment
Pollution degree:
Pollution degree 1 and 2
Pollution degree 3 and 4
See Table 15 on page 91
for descriptions
of pollution degree rating.
All enclosures are acceptable for pollution degree 1 and 2.
An enclosure that meets or exceeds IP54, NEMA/UL Type 12, is
required for pollution degree 3 and 4.
Table 13 - Certifications (continued)
Certifications
(1)
Description Frames
A…E
240…480V
A…E
600V