146 Rockwell Automation Publication 7000-UM202D-EN-P - May 2018
Chapter 3 Control Component Definition and Maintenance
Terminal/Connections Descriptions
P1 – DC Input PIN NO. LABEL DESCRIPTION ONLY
1 +56V +56V input
2 +56V COMM +56V common
3 EARTH earth ground
P2 – SENSE
(To ACB)
PIN NO. LABEL DESCRIPTION ONLY
1 +56V +56V input supply
2 +56V RTN +56V input supply return
3 NC Not connected
4 NC Not connected
5 +24V Isolated +24V supply
6 +24V RTN Isolated +24V supply return
7 NC Not connected
8 NC Not connected
9 +5VA Primary +5V supply, before OR’ing diode
10 DGND(com1) +5V, +/-15V common
11 +5VB Secondary +5V supply, before OR’ing diode
12 DGND(com1) +5V, +/-15V common
13 ID0 Power supply ID Pin 0
14 ID1 Power supply ID Pin 1
P3 – ISOLATOR
(To Isolator
Modules)
PIN NO. LABEL DESCRIPTION ONLY
1 ISOLATOR (+24V,1A) +24V,1A/com4
2 ISOL_COMM (com4) 0V/com4
3 EARTH EARTH
P4 – PWR (To
ACB)
PIN NO. LABEL DESCRIPTION ONLY
1 +24V_XIO (+24V,2A) +24V,2A/com3
2 XIO_COMM (com3) 0V/com3
3 +HECSPWR (+24V,1A) +24V,1A/com2
4 LCOMM (com2) 0V/com2
5 –HECSPWR (-24V,1A) -24V,1A/com2
6 +15V_PWR (+15V,1A) +15V,1A/com1
7 ACOMM (com1) 0V/com1
8 –15V_PWR (-15V,1A) -15V,1A/com1
9 +5V_PWR (+5V,5A) +5V,5A/com1
10 DGND (com1) 0V/com1
11 EARTH earth ground