142 Rockwell Automation Publication 750-IN100B-EN-P - July 2017
Chapter 6 I/O Wiring
Safety Enable Circuitry
The drive ships with the safety enable jumper (SAFETY) installed. This
jumper must be removed when using the safe torque off or speed monitoring
safety options.
Figure 68 - SAFETY Jumper Location
IMPORTANT Failure to remove the jumper when using either safety option will cause the
drive to fault when a start command is issued.