154 Rockwell Automation Publication 750-IN100B-EN-P - July 2017
Chapter 6 I/O Wiring
22-Series I/O Module
Table 30 - Input Mode Jumpers
Table 29 - 11-Series I/O Relay Wiring Examples
Input/Output Connection Example Required Parameter Changes
Relay Output
External supply
11-Series I/O Module • Set Selection
Port nn:10 [RO0 Sel] (11-Series I/O Module) = Port 10/11:354 [Motor Side Sts 1], bit 7 =
Faulted
•View Results
Port nn:5 [Dig Out Sts] (11-Series I/O Module)
Power
Source
or
R0NO
20-750-2262C-2R (24 Volts DC)
20-750-2263C-1R2T
Jumper
Position
Voltage Mode Current Mode