Rockwell Automation Publication 750-IN100B-EN-P - July 2017 151
I/O Wiring Chapter 6
3-Wire Control
External 24 volt supply
20-750-1132C-2R
20-750-1133C-1R2T
11-Series I/O Module TB1
•Set Selection
Port 00:108 [DI M Stop] = Port nn:1 [Dig In Sts], bit 0 = Input 0 (11-Series I/O Module)
Port 00:117 [DI M Start] = Port nn:1 [Dig In Sts], bit 1 = Input 1 (11-Series I/O Module)
• View Results
Port nn:1 [Dig In Sts] (11-Series I/O Module)
Port 10/11:354 [Motor Side Sts 1]
3-Wire Control
External 120 volt supply
20-750-1132D-2R
11-Series I/O Module TB1
•Set Selection
Port 00:108 [DI M Stop] = Port nn:1 [Dig In Sts], bit 0 = Input 0 (11-Series I/O Module)
Port 00:117 [DI M Start] = Port nn:1 [Dig In Sts], bit 1 = Input 1 (11-Series I/O Module)
• View Results
Port nn:1 [Dig In Sts] (11-Series I/O Module)
Port 10/11:354 [Motor Side Sts 1]
Table 28 - 11-Series I/O Module TB1 Wiring Examples (continued)
Input/Output Connection Example Required Parameter Changes
Di0P
Di1P
Di0P
Di1P