Fire Reports
Selecting Yes enables a report to be sent when the
event occurs.
Table 9: Diagnostic Reports
Report Selections Description
R# Fire Alarm
Yes, No
Reports Fire Event.
R# Fire Restore
(Alarm)
Yes, No
Reports fire restoral
from alarm.
R# Fire Missing
Yes, No
Reports missing Fire
point.
R# Fire Trouble
Yes, No
Reports fire trouble.
R# Fire
Supervis
Yes, No
Reports fire
supervision.
R# Fire Restore
(T/M/S)
Yes, No
Reports fire restoral
from trouble,
missing, or bypass.
R# Fire Cancel
Yes, No
Reports canceled
fire alarm.
R# Fire Sup
Miss
Yes, No
Report fire
supervisory missing.
R# Fire Supv
Rest
*
Yes, No
Reports restorals
from Fire
Supervision.
* This event is not reported when using BFSK format.
Burglar Reports
Selecting Yes enables sending a report when the
event occurs.
Table 10: Burglar Reports
Report Selections Description
R# Alarm
Yes, No
Report Burglar Alarm
Event.
R# Burg
Restore
Yes, No
Reports non-fire
restoral from trouble,
missing, or
supervisory.
R# Duress
Yes, No
Duress Report.
R# Missing
Alarm
Yes, No
Reports missing
Alarm point.
R# Usr Code
Tmpr
Yes, No
Reports user code
tamper.
R# Trouble Rpt
Yes, No
Reports Trouble
Event.
R# Missing Trbl
Yes, No
Reports Missing
Trouble Event.
R# Non Fire
Suprv
Yes, No
Reports Non-fire
Supervision Event.
R# Pt Bus Fail
Yes, No
Reports point bus
failure.
R# Pt Bus Rstl
Yes, No
Reports restoral of
point bus after failure.
R# Non Fire
Cncl
Yes, No
Reports canceled
non-fire alarm.
R# Alarm
Restore
Yes, No
Reports non-fire
restoral from alarm.
R# Sup Missing
Yes, No
Reports supervisory
missing.
R# Unverfied
Evt
†*
Yes, No
Reports Unverified
Events for Cross
points.
This event is not reported when using BFSK format.
* This event does not produce a corresponding Restoral
Event.
0101
0101
0101
The Unverified Event is transmitted when a
single point programmed in Cross Point
Group faults into an alarm condition then
restores before the Cross Point Time
elapses. This event encompasses both
Fire and Non-fire points. It is not, however,
related to the Verify Time used for smoke
detectors.

Table of Contents

Other manuals for Bosch D7412G

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bosch D7412G and is the answer not in the manual?

Bosch D7412G Specifications

General IconGeneral
Partitions8
Power Supply16.5 VAC, 40 VA
User Codes99
Users99
Communication FormatsContact ID, SIA
Operating Temperature0°C to +49°C (32°F to +120°F)

Related product manuals