Service Check Function SiBE121123_A
145 Service Diagnosis
3.1.3 ARC433 Series Remote Controller
Check Method 1 1. When the timer cancel button is held down for 5 seconds,
00
is displayed on the temperature
display screen.
2. Press the timer cancel button repeatedly until a long beep sounds.
îš„
The code indication changes in the sequence shown below.
<ARC433A85, A87, A89>
<ARC433B67, B69>
Note: 1. A short beep and two consecutive beeps indicate non-corresponding codes.
2. To return to the normal mode, hold the timer cancel button down for 5 seconds. When the
remote controller is left untouched for 60 seconds, it also returns to the normal mode.
3. Not all the error codes are displayed. When you cannot find the error code, try the check
method 2. (→ Refer to page 146.)
Timer cancel button
(R14555)
< ARC433 Series >
No. Code No. Code No. Code
1 00 12 F6 23 A1
2 U4 13 C7 24 E1
3 L5 14 A3 25 UA
4 E6 15 H8 26 UH
5 H6 16 H9 27 P4
6 H0 17 C9 28 L3
7 A6 18 C4 29 L4
8 E7 19 C5 30 H7
9 U0 20 J3 31 U2
10 F3 21 J6 32 EA
11 A5 22 E5 33 AH
No. Code No. Code No. Code
1 00 12 C7 23 H0
2 U4 13 H8 24 E1
3 F3 14 J3 25 P4
4 E6 15 A3 26 L3
5 L5 16 A1 27 L4
6 A6 17 C4 28 H6
7 E5 18 C5 29 H7
8 F6 19 H9 30 U2
9 C9 20 J6 31 UH
10 U0 21 UA 32 EA
11 E7 22 A5 33 AH