Troubleshooting for Outdoor Unit SiBE121123_A
185 Service Diagnosis
7.4 Unspecified Voltage (between Indoor Unit and Outdoor
Unit) / Anti-icing Control in Other Room
Error Code
UA, UH
Method of Error
Detection
A wrong connection is detected by checking the combination of indoor and outdoor units on the
microcomputer.
Error Decision
Conditions
Anti-icing control in other room
Unspecified internal and/or external voltages
Mismatching of indoor and outdoor units
Supposed
Causes
Anti-icing control in other room
Wrong models interconnected
Wrong indoor unit PCB or outdoor unit PCB mounted
Troubleshooting
Note: Refer to “Anti-icing control for indoor unit” on page 186 for detail.
(R16018)
Caution
NO
YES
NO
YES
NO
YES
Check the model combination.
Check the combination of all the
models being connected.
The anti-icing function is
activated in other rooms.
Refer to A5.
Correct the supply voltage.
Match the compatible models.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Error displayed while
operating?
Supply voltage as
specified?
Matched compatibly?

Table of Contents

Other manuals for Daikin 2AMX40G3V1B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 2AMX40G3V1B and is the answer not in the manual?

Daikin 2AMX40G3V1B Specifications

General IconGeneral
BrandDaikin
Model2AMX40G3V1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals