SiBE041101 Check
Service Diagnosis 126
5.5 Installation Condition Check
Check No.07
5.6 Discharge Pressure Check
Check No.08
Installation condition check
Normal
Check the allowable
dimensions of the air
suction and
discharge area.
Is the airflow blocked by
obstacles or winds
blowing in the opposite
direction?
(R9459)
Abnormal
YES
YES
YES
Is the discharged air
short-circuited?
NO
NO
NO
Is the outdoor heat
exchanger very dirty?
Change the installation
location or direction.
Change the installation
location or direction.
Clean the outdoor heat
exchanger.
Change the installation
location or direction.
Check the outdoor temperature.
(The outdoor temperature
should be 46˚C or lower.)
(R11718)
Not dirty
YES
YES
Dirty
NO
NO
NO
YES
Is the air
filter or indoor / outdoor
heat exchanger
dirty?
Is the connection pipe
deformed?
Is the stop valve open?
High?
Replace the compressor.
Open the stop valve.
Replace the pipe installed at
the site.
Clean the dirty one.
Replace the compressor.
Discharge pressure check

Table of Contents

Other manuals for Daikin J-Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin J-Series and is the answer not in the manual?

Daikin J-Series Specifications

General IconGeneral
BrandDaikin
ModelJ-Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals