SiBE041101 Troubleshooting
Service Diagnosis 84
4.4 Fan Motor (DC Motor) or Related Abnormality
Remote
Controller
Display
A6
Method of
Malfunction
Detection
The rotation speed detected by the Hall IC during fan motor operation is used to determine
abnormal fan motor operation.
Malfunction
Decision
Conditions
The detected rotation speed does not reach the demanded rotation speed of the target tap, and
is less than 50% of the maximum fan motor rotation speed.
Supposed
Causes
Layer short inside the fan motor winding
Breaking of wire inside the fan motor
Breaking of the fan motor lead wires
Defective capacitor of the fan motor
Defective indoor unit PCB