SiBE041101 Control Specification
Function and Control 38
3.3 Controls at Mode Changing / Start-up
3.3.1 Preheating Operation
Outline The inverter operation in open phase starts with the conditions of the preheating command from
the indoor unit, the outdoor temperature, and the discharge pipe temperature.
Detail
RK(X)S20/25/35J2V1B
Outdoor temperature
7°C
Control A
Outdoor temperature < 7°C
Control B
Control A
ON condition
Discharge pipe temperature < 10°C
OFF condition
Discharge pipe temperature > 12°C
Radiation fin temperature
90°C
Control B
ON condition
Discharge pipe temperature < 20°C
OFF condition
Discharge pipe temperature > 22°C
Radiation fin temperature
90°C
RK(X)S42J2V1B
ON Condition
When the discharge pipe temperature is below 10ºC, the inverter operation in open phase
starts.
OFF Condition
When the discharge pipe temperature is higher than 12ºC, the inverter operation in open
phase stops.
RK(X)S50J2V1B
Outdoor temperature
10°C
Control A
Outdoor temperature < 10°C
Control B
Control A
ON condition
Discharge pipe temperature < 6°C
OFF condition
Discharge pipe temperature > 8°C
Radiation fin temperature
90°C
Control B
ON condition
Discharge pipe temperature < 10.5°C
OFF condition
Discharge pipe temperature > 12°C
Radiation fin temperature
90°C

Table of Contents

Other manuals for Daikin J-Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin J-Series and is the answer not in the manual?

Daikin J-Series Specifications

General IconGeneral
BrandDaikin
ModelJ-Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals