Troubleshooting for RA Indoor Unit SiBE121135_A
173 Service Diagnosis
5.3 Fan Motor or Related Abnormality
5.3.1 DC Motor (Wall Mounted Type, Floor Standing Type)
Error Code A6
Method of Error
Detection
The rotation speed detected by the Hall IC during fan motor operation is used to determine
abnormal fan motor operation.
Error Decision
Conditions
The detected rotation speed does not reach the demanded rotation speed of the target tap, and
is less than 50% of the maximum fan motor rotation speed.
Supposed
Causes
Supply voltage is not as specified.
Layer short inside the fan motor winding
Breaking of wire inside the fan motor
Breaking of the fan motor lead wires
Defective capacitor of the fan motor
Defective indoor unit PCB