SiBE121135_A Troubleshooting for Outdoor Unit
Service Diagnosis 204
7.3 Signal Transmission Error (on Outdoor Unit PCB)
Error Code U7
Outdoor Unit LED
Display
A j 1 h 2 i 3 i 4 i 5 h
LED5 is equipped only on the 5-room model.
Method of Error
Detection
Communication error between microcomputer mounted on the main PCB and PM1.
Error Decision
Conditions
The abnormality is determined when the data sent from the PM1 can not be received for 9
seconds.
The error counter is reset when the data from the PM1 can be successfully received.
Supposed
Causes
Defective outdoor unit PCB
Troubleshooting
(R7185)
Caution
NO
YES
Turn off the power and turn it on
again.
Replace the outdoor unit
PCB.
The cause can be an
external factor other than
the malfunction.
Observe the operating
condition in long term.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Error again?

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Super multi NX E Series and is the answer not in the manual?

Daikin Super multi NX E Series Specifications

General IconGeneral
BrandDaikin
ModelSuper multi NX E Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals