SiBE121135_A Troubleshooting for SA Indoor Unit
Service Diagnosis 196
6.7 Remote Controller Thermistor Abnormality
Error Code CJ
Method of Error
Detection
Even if remote controller thermistor is faulty, system is possible to operate by system thermistor.
Malfunction detection is carried out by the temperature detected by remote controller thermistor.
Error Decision
Conditions
The remote controller thermistor is disconnected or shorted while the unit is running.
Supposed
Causes
îš„ Defective thermistor
îš„ Broken wire
Troubleshooting
Note: To delete the record of error codes, press the [ON/OFF] button for 4 seconds or more while the
error code is displayed in the inspection mode.
Replace the remote
controller.
External factor other
than equipment
malfunction.
(for example, noise
etc.)
YES
NO
(R18062)
Is CJ
displayed on the
remote controller
again?
Delete the record of error
codes. (See the Note.)
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Super multi NX E Series and is the answer not in the manual?

Daikin Super multi NX E Series Specifications

General IconGeneral
BrandDaikin
ModelSuper multi NX E Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals