20.0
15.0
10.0
5.0
0.0V
-5.0
-10.0
-15.0
-20.0
-100.0 us 5 us/Div.
Input A
130BX146.10
Illustration 8.16 Gate Signal Waveform from Gate Drive Card
IGBT gate signal measured on the gate drive card: 5 V per
division vertical scale, 50 ms per division time scale. Unit
running at 30 Hz.
An incorrect reading of a gate signal indicates that the
gate drive card is defective or the signal has been lost
before arriving at the gate card. The gate signals can then
be checked with the signal test board to verify their
presence from the control card to the power card as
follows.
1. Insert the signal test board into power card
connector MK104.
2. With scope probe common connected to terminal
4 (common) of the signal board, measure 6 gate
signals at signal board terminals 25–30.
3. Place the drive in run mode at 30 Hz.
The waveform in Illustration 8.17 is the correct result.
8.00
6.00
4.00
2.00
0.00V
-2.00
-4.00
-6.00
-8.00
-100.0us
Input A
130BX147.10
5 us/Div.
Illustration 8.17 Gate Signal Waveform from Signal Test Board
Test Procedures Service Guide
MG94A502 Danfoss A/S © 02/2019 All rights reserved. 113
8 8

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 300 Series and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 300 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 300 Series
CategoryDC Drives
LanguageEnglish

Related product manuals