[73] Logic Rule 3
See parameter group 13-4* Logic Rules. If
logic rule 3 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[74] Logic Rule 4
See parameter group 13-4* Logic Rules. If
logic rule 4 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[75] Logic Rule 5
See parameter group 13-4* Logic Rules. If
logic rule 5 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[80] SL Digital
Output A
See 13-52 SL Controller Action. The output
goes high whenever the smart logic action
[38] Set dig. out. A high is executed. The
output goes low whenever the smart logic
action [32] Set dig. out. A low is executed.
[81] SL Digital
Output B
See 13-52 SL Controller Action. The input
goes high whenever the smart logic action
[39] Set dig. out. A high is executed. The
input goes low whenever the smart logic
action [33] Set dig. out. A low is executed.
[82] SL Digital
Output C
See 13-52 SL Controller Action. The input
goes high whenever the smart logic action
[40] Set dig. out. A high is executed. The
input goes low whenever the Smart Logic
Action [34] Set dig. out. A low is executed.
[83] SL Digital
Output D
See 13-52 SL Controller Action. The input
goes high whenever the smart logic action
[41] Set dig. out. A high is executed. The
input goes low whenever the smart logic
action [35] Set dig. out. A low is executed.
[84] SL Digital
Output E
See 13-52 SL Controller Action. The input
goes high whenever the smart logic action
[42] Set dig. out. A high is executed. The
input goes low whenever the smart logic
action [36] Set dig. out. A low is executed.
[85] SL Digital
Output F
See 13-52 SL Controller Action. The input
goes high whenever the smart logic action
[43] Set dig. out. A high is executed. The
input goes low whenever the smart logic
action [37] Set dig. out. A low is executed.
[120] Local
reference
active
Output is high when 3-13 Reference Site =
[2] Local or when 3-13 Reference Site = [0]
Linked to hand auto at the same time as
the LCP is in [Hand on] mode.
Reference site set
in 3-13 Reference
Site
Local
reference
active
[120]
Remote
reference
active [121]
Reference site:
Local
3-13 Reference
Site [2]
1 0
Reference site:
Remote
3-13 Reference
Site [1]
0 1
Reference site:
Linked to Hand/
Auto
Hand 1 0
Hand off
1 0
Auto off
0 0
Auto 0 1
Table 6.8 Local and Remote Reference
[121] Remote
reference
active
Output is high when 3-13 Reference Site
=[1] Remote or [0] Linked to hand/auto
while the LCP is in [Auto on] mode. See
Table 6.8.
[122] No alarm Output is high when no alarm is present.
[123] Start
command
active
Output is high when there is an active
start command (via digital input bus
connection or [Hand on] or [Auto on]), and
no stop or start command is active.
[124] Running
reverse
Output is high when the frequency
converter is running counter clockwise
(the logical product of the status bits
‘running’ and ‘reverse’).
[125] Drive in hand
mode
Output is high when the frequency
converter is in [Hand on] mode (as
indicated by the LED light above [Hand
on]).
[126] Drive in auto
mode
Output is high when the frequency
converter is in [Hand on] mode (as
indicated by the LED light above [Auto
on]).
[151] ATEX ETR cur.
alarm
Selectable if parameter 1-90 Motor Thermal
Protection is set to [20] Above feedback
high or [21] Thermal warning. If the alarm
164 ATEX ETR cur.lim.alarm is active, the
output is 1.
[152] ATEX ETR freq.
alarm
Selectable if parameter 1-90 Motor Thermal
Protection is set to [20] Above feedback
high or [21] Thermal warning. If the alarm
166 ATEX ETR freq.lim.alarm is active, the
output is 1.
[153] ATEX ETR cur.
warning
Selectable ifparameter 1-90 Motor Thermal
Protection is set to [20] Above feedback
high or [21] Thermal warning. If the alarm
Programming Operating Instructions
66 Danfoss A/S © Rev. 2014-07-29 All rights reserved. MG37A202