Installation and Operation Manual for Inverter RPI M50A_12s V1 EU EN 2017-03-09
8 Settings
8.5.3 P (V) (regulating the active power via the
grid voltage)
These parameters are set according to the
requirements of the selected country. Changing
these parameter settings can invalidate the type
approval of the unit. Change this setting only after
consultation with Delta customer service.
Overview
This function allows you to regulate the active power fed into the
grid via the grid voltage.
Setting options
Parameter Description Setting range
Mode
Switch the function on and off.
ON|OFF
P lock-in 10 .. 100%
P lock-out 0 .. 50%
V lock-in 230.0 .. 292.0 V
V lock-out 207.0 .. 292.0 V
T Restart 10 .. 900 s
Menu item path
Main Menu > Active/Reactive Pwr > Active Power Ctrl >
P(V)
Calling up the menu item
Status: On Grid
10.Sep 2014 15:32
1. If the default information is displayed, press any button to open the main menu.
Otherwise, press the
EXIT
button repeatedly until the main menu is displayed.
Inverter Info.
General Settings
Install Settings
2. Use the and buttons to select the Active/Reactive Pwr entry and then press
the
ENT
button.
energy production.
Adj. would affect
3. This function is protected with password 5555.
Use the
and buttons to set the individual numerals.
Press the
ENT
button to confirm a number.
Reactive Power Ctrl
Active Power Ctrl
4. Use the and buttons to select the Active Power Ctrl entry and then press the
ENT
button.
P(V)
Power vs. Frequency
Power Limit
5. Use the and buttons to select the P(V) entry and then press the
ENT
button.