Installation and Operation Manual for Inverter RPI M50A_12s V1 EU EN 2017-03-09
8 Settings
8.5.4 Constant cos phi (cos φ)
These parameters are set according to the
requirements of the selected country. Changing
these parameter settings can invalidate the type
approval of the unit. Change this setting only after
consultation with Delta customer service.
Overview
Thisfunctionallowsyoutosetaconstantcosφ.
Setting options
Parameter Description Setting range
Mode
Switch the function on and off.
ON|OFF
Cos Phi
Constantcosphi(cosφ),capacitiveorinductive
0.80 .. 0.99 cap
1
0.80 .. 0.99 ind
Menu item path
Main Menu > Active/Reactive Pwr > Reactive Power Ctrl >
Constant cosphi
Calling up the menu item
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1. If the default information is displayed, press any button to open the main menu.
Otherwise, press the
EXIT
button repeatedly until the main menu is displayed.
Inverter Info.
General Settings
Install Settings
2. Use the and buttons to select the Active/Reactive Pwr entry and then press
the
ENT
button.
Password 0 * * *
energy production.
Adj. would affect
Warning:
3. This function is protected with password 5555.
Use the
and buttons to set the individual numerals.
Press the
ENT
button to confirm a number.
Reactive Power Ctrl
Active Power Ctrl
4. Use the and buttons to select the Reactive Power Ctrl entry and then press
the
ENT
button.
Constant Q
Cos phi (P)
5. Use the and buttons to select the Constant cos phi entry and then press the
ENT
button.