5 Planning installation
5.12 Using external grid and system protec-
tion
1. The German standard VDE-AR-N 4105, Section 6.1, requires
external grid and system protection with a coupling switch for
PV system larger than 30 kVA.
2. Alternatively, VDE-AR-N 4105, Section 6.4.1, allows the
use of an inverter with an internal coupling switch when this
switch disconnects the inverter from the grid in less than
100 ms.
This inverter satisfies the requirements of (2) when the following
firmwareversionsareinstalled:DSP≥1.30/
RED≥1.20/COMM≥1.10.Externalgridandsystemprotection
is not necessary for inverters with these firmware versions.
5.13 Connecting a PC
The inverter settings can be changed using a PC. This requires
the following accessories.
Accessories Description
Standard USB/RS485 adapter
For connecting a PC to the
inverter
Delta Service Software
For changing the inverter
settings
The Delta Service Software can be downloaded from www.
solar-inverter.com.
Cable requirements
Bell wire. Both ends open.

Table of Contents

Other manuals for Delta RPI M50A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta RPI M50A and is the answer not in the manual?

Delta RPI M50A Specifications

General IconGeneral
BrandDelta
ModelRPI M50A
CategoryInverter
LanguageEnglish

Related product manuals