Installation and Operation Manual for Inverter RPI M50A_12s V1 EU EN 2017-03-09
8 Settings
8.4.4.5 P Ramp Up
These parameters are set according to the
requirements of the selected country. Changing
these parameter settings can invalidate the type
approval of the unit. Change this setting only after
consultation with Delta customer service.
Overview
This function allows you to specify the active power increase
ramp for cases where the inverter disconnects from the grid due
to a voltage fault or frequency fault.
Once the fault has disappeared, the inverter continuously
increases the active power according to the specified ramp.
Setting options
Parameter Description Setting range
P Ramp Up
Increase of the fed active power in percent per min-
ute.
0 .. 6000 %/min
Menu item path
Main Menu > Install Settings > Grid Settings > P
Ramp Up
Setting the active power increase ramp
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1. If the default information is displayed, press any button to open the main menu.
Otherwise, press the
EXIT
button repeatedly until the main menu is displayed.
Inverter Info.
General Settings
Install Settings
Active/Reactive Pwr
FRT
2. Use the and buttons to select the Install Settings entry and then press the
ENT
button.
Password 0 * * *
energy production.
Adj. would affect
Warning:
3. Enter the password provided by Delta customer service.
Use the
and buttons to set the individual numerals.
Press the
ENT
button to confirm a number.
Grid Settings
Country
Insulation
Inverter ID: 001
4. Use the and buttons to select the Grid Settings entry and then press the
ENT
button.
Freq. Protection
Reconnect T: 600s
P Ramp up: 6000%/m
Voltage Protection
5. Use the and buttons to select the P Ramp Up entry and then press the
ENT
but-
ton.
The shape of the arrow changes
, the value can be changed.
The currently set value is displayed after the entry.
Freq. Protection
Reconnect T: 600s
P Ramp up: 6000%/m
Voltage Protection
6. Use the and buttons to configure the value and then press the
ENT
button.

Table of Contents

Other manuals for Delta RPI M50A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta RPI M50A and is the answer not in the manual?

Delta RPI M50A Specifications

General IconGeneral
BrandDelta
ModelRPI M50A
CategoryInverter
LanguageEnglish

Related product manuals