5 Planning installation
Installation and Operation Manual for Inverter RPI M50A_12s V1 EU EN 2017-03-09
42
5.14 Tools and materials required
This sections lists the necessary tools and materials not included in the scope of delivery.
5.14.1 For mounting the inverter
Part Quantity Description
M6 mounting screws 6 or 12
The mounting plate must be attached using 6 or 12 M6 screws.
Additional mounting materials may be required depending on the installation
position of the inverter (e.g. brick wall, concrete wall, metal frame etc.): Dow-
els, washers, lock washers, nuts etc.
Always take the conditions at the installation location into account when
selecting the mounting materials.
Galvanic corrosion can occur when using mounting materials made of differ-
ent materials
5.14.2 For connecting to the grid (AC)
Part Quantity Description
AC cable -
See “5.6.4 Cable requirements”, page 30 for notes on selecting the AC
cable.
Wire end-sleeves 5
Wire end-sleeves must be used at the wire ends of the AC cable to ensure
adequate electrical contact between the AC plug and the AC cable.
Attach the wire end-sleeves to the wires using a crimping tool.