6 Installation
6.5.4 Connecting an external alarm unit
Cable and wiring requirements
Shielded twisted-pair cable with solid conductors (CAT 5 or
CAT 6.
Cable diameter: 5 mm
Wire cross-section: 1 mm
2
Lay the cable with a suitable clearance to the AC and DC
cables to prevent interference in the data connection.
6.5.4.1 Wiring for an external alarm unit with an external
12 V
DC
power supply
The external alarm unit must be connected to an external power
supply if the internal 12V
DC
power supply is not used.
A B
Dry contacts plug
Strobe light Buzzer
Fig. 6.15: Connection example: Dry contacts with an external
power supply
1. Connect two wires of the cable to one of the two dry con-
tacts.
2. After commissioning, use the inverter display to assign an
event for triggering the alarm unit (see “8.4.6 Dry contacts”,
page 98).