93
Installation and Operation Manual for Inverter RPI M50A_12s V1 EU EN 2017-03-09
8 Settings
8.4.4.4 Reconnection time
These parameters are set according to the
requirements of the selected country. Changing
these parameter settings can invalidate the type
approval of the unit. Change this setting only after
consultation with Delta customer service.
Overview
To change this setting, you need a special
password provided by Delta customer service.
You can find the contact information on the back
of this document.
This function allows you to specify a reconnection time for cases
where the inverter disconnects from the grid due to a voltage
fault or frequency fault.
Once the fault has disappeared, the inverter waits for the speci-
fied reconnection time before reconnecting to the grid.
Setting options
Parameter Description Setting range
Reconnect T
Reconnection time
0 .. 600 s
Menu item path
Main Menu > Install Settings > Grid Settings > Re-
connect T
Setting the reconnection time
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1. If the default information is displayed, press any button to open the main menu.
Otherwise, press the
EXIT
button repeatedly until the main menu is displayed.
Inverter Info.
General Settings
Install Settings
Active/Reactive Pwr
FRT
2. Use the and buttons to select the Install Settings entry and then press the
ENT
button.
Password 0 * * *
energy production.
Adj. would affect
Warning:
3. Enter the password provided by Delta customer service.
Use the
and buttons to set the individual numerals.
Press the
ENT
button to confirm a number.
Grid Settings
Country
Insulation
Inverter ID: 001
4. Use the and buttons to select the Grid Settings entry and then press the
ENT
button.
Freq. Protection
Reconnect T: 600s
P Ramp up: 6000%/m
Voltage Protection
5. Use the and buttons to select the Reconnect T entry and then press the
ENT
button.
The shape of the arrow changes
, the value can be changed.
The currently set value is displayed after the entry.

Table of Contents