8 Settings
Installation and Operation Manual for Inverter RPI M50A_12s V1 EU EN 2017-03-09
92
Changing the settings
This procedure is the same for all parameters.
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1. If the default information is displayed, press any button to open the main menu.
Otherwise, press the
EXIT
button repeatedly until the main menu is displayed.
Inverter Info.
General Settings
Install Settings
2. Use the and buttons to select the Install Settings entry and then press the
ENT
button.
energy production.
Adj. would affect
3. Enter the password provided by Delta customer service.
Use the
and buttons to set the individual numerals.
Press the
ENT
button to confirm a number.
Country
Insulation
4. Use the and buttons to select the Grid Settings entry and then press the
ENT
button.
Freq. Protection
Reconnect T: 600s
P Ramp up: 6000%/m
Voltage Protection
5. Use the and buttons to select the Freq. Protection entry and then press the
ENT
button.
High On: 50.05Hz
High Off T: 0.1s
Low Off: 47.50Hz
High Off: 51.50Hz
6. Use the and buttons to select a parameter and then press the
ENT
button.
→ The shape of the arrow changes
, the value can be changed.
The currently set value is displayed after the entry.
7. Use the and buttons to configure the value and then press the
ENT
button.