Installation and Operation Manual for Inverter RPI M50A_12s V1 EU EN 2017-03-09
8 Settings
Setting options
Parameter Description Setting range
High Off
Voltage high off
184.0 .. 276.0 V
High On
Voltage high on
184.0 .. 276.0 V
High Off T
Disconnection time for voltage high off
0.0 .. 5.0 s
Low Off
Voltage low off
184.0 .. 276.0 V
Low On
Voltage low on
184.0 .. 276.0 V
Low Off T
Disconnection time for voltage low off
0 .. 5.0 s
Hi Off Slow
Voltage high off slowly
184.0 .. 276.0 V
Lo On Slow
Voltage low on slowly
184.0 .. 276.0 V
Hi Off Sl T
Disconnection time for voltage high off slowly
0 .. 600 s
Lo Off Slow
Voltage low off slowly
184.0 .. 276.0 V
Lo On Slow
Voltage low on slowly
184.0 .. 276.0 V
Lo Off Sl T
Disconnection time for voltage low off slowly
0 .. 600 s
Menu item path
Main Menu > Install Settings > Grid Settings > Volt-
age Protection
Changing the settings
This procedure is the same for all parameters.
E-Today: 0kWh
Power: 0W
Status: On Grid
10.Sep 2014 15:32
1. If the default information is displayed, press any button to open the main menu.
Otherwise, press the
EXIT
button repeatedly until the main menu is displayed.
Inverter Info.
General Settings
Install Settings
2. Use the and buttons to select the Install Settings entry and then press the
ENT
button.
energy production.
Adj. would affect
3. Enter the password provided by Delta customer service. Use the and buttons to
set the individual numerals.
Press the
ENT
button to confirm a number.
Country
Insulation
4. Use the and buttons to select the Grid Settings entry and then press the
ENT
button.