EasyManuals Logo

GE AF-650 GP Design And Installation Guide

GE AF-650 GP
166 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #128 background imageLoading...
Page #128 background image
12 Terminal and Applicable Wire
12.1 Cables
Power [kW / HP] Enclosur
e
Line power Motor Load share Brake Ground *
200–240V 380–480V 525–600V 525–690V
Tightenin
g torque
[Nm / in-
lbs]
Wire size
[mm2
(AWG)]
Tighteni
ng
torque
[Nm / in-
lbs]
Wire size
[mm2
(AWG)]
Tightenin
g torque
[Nm / in-
lbs]
Wire size
[mm2
(AWG)]
Tightenin
g torque
[Nm / in-
lbs]
Wire size
[mm2
(AWG)]
Tightening
torque
[Nm / in-
lbs]
0.25–
2.2kW
0.33–3HP
0.37–4kW
0.5–5HP
0.75–4kW
1–5HP
IP20
1.8 / 16
4 (10)
1.8 / 16
4 (10)
1.8 / 16
4 (10)
1.8 / 16
4 (10)
3 / 27
3.7kW 5HP
5.5–7.5kW
7.5–10HP
5.5–7.5kW
7.5–10HP
IP20
0.25–
3.7kW
0.33–5HP
0.37–7.5kW
0.5–10HP
0.75–7.5kW
1–10HP
IP55 or
IP66
5.5–7.5kW
7.5–10HP
11–15kW
15–20HP
11–15kW
15–20HP
IP20
16 (6) 16 (6) 16 (6) 16 (6)
5.5–7.5kW
7.5–10HP
11–15kW
15–20HP
11–15kW
15–20HP
IP55 or
IP66
1.5 / 14 1.5 / 14
11–15kW
15–20HP
18.5–30kW
25–40HP
18.5–30kW
25–40HP
IP20
4.5 / 40 35 (2) 4.5 / 40 35 (2)
4.5 / 40
35 (2)
4.5 / 40
35 (2)
11kW
15
HP
18.5
–22kW
25–30HP
18.5–22kW
25–30HP
11–22kW
15–30HP
IP55 or
IP66
3.7 / 33 3.7 / 33
18.5–22kW
25–30HP
37–45kW
50–60HP
37–45kW
50–60HP
IP20
10 / 89
50 (1)
10 / 89
50 (1)
10 / 89
50 (1)
10 / 89
50 (1)
15–22kW
20–30HP
30–45kW
40–60HP
30–45kW
40–60HP
IP55 or
IP66
90 (3/0) 90 (3/0) 90 (3/0) 90 (3/0)
30–37kW
40–50HP
55–75kW
75–100HP
55–75kW
75–100HP
IP20
14 / 124
150 (300
mcm)
14 / 124
150 (300
mcm)
14 / 124
95 (4/0)
14 / 124
95 (4/0)
30–37kW
40–50HP
55–75kW
75–100HP
55–75kW
75–100HP
30–75kW
40–100HP
IP55 or
IP66
120 (4/0) 120 (4/0) 120 (4/0) 120 (4/0)
90–110kW
125–150HP
90–132kW
125–200HP
all
19 / 168
2x70
(2x2/0)
19 / 168
2x70 (2x2/0)
9.5 / 84
2x70
(2x2/0)
9.5 / 84
2x70 (2x2/0)
19 / 168
132–200kW
200–350HP
160–315kW
250–400HP
all
2x185
(2x350mcm
)
2x185
(2x350mcm)
2x185
(2x350mc
m)
2x185
(2x350mcm)
250–400kW
350–550HP
35
5–56
0kW
500–750HP
all
4x240
(4x500mcm
)
4x240
(4x500mcm)
19 / 168
4x240
(4x500mc
m)
450–630kW
600–900HP
630–800kW
900–1150HP
all
8x240
(8x500mcm
)
8x150
(8x300mcm)
4x120
(4x250mc
m)
4x185
(4x350mcm)
710–800kW
1000–
1200HP
900–1000kW
1250–
1350HP
all
12x150
(12x300mc
m)
6x185
(6x350mcm)
* Maximum cable size according to national code
Table 12.1
Terminal and Applicable Wir...
AF-650 GP
TM
Design and Installation Guide
DET-767A 12-1
12 1
2

Table of Contents

Other manuals for GE AF-650 GP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE AF-650 GP and is the answer not in the manual?

GE AF-650 GP Specifications

General IconGeneral
BrandGE
ModelAF-650 GP
CategoryDC Drives
LanguageEnglish

Related product manuals