Initialization of the adjustable frequency drive to
restore factory default settings does not change
data stored in the keypad memory
WARNING
UNINTENDED START!
When the adjustable frequency drive is connected to AC
line power, the motor may start at any time. The
adjustable frequency drive, motor, and any driven
equipment must be in operational readiness. Failure to be
in operational readiness when the adjustable frequency
drive is connected to AC line power could result in death,
serious injury, or equipment or property damage.
4.2.1 Uploading Data to the Keypad
1. Press [Off] to stop the motor before uploading or
downloading data.
2. Go to K-50 Keypad Copy.
3. Press [OK].
4. Select All to keypad.
5. Press [OK]. A progress bar shows the uploading
process.
6. Press [Hand] or [Auto] to return to normal
operation.
4.2.2 Downloading Data from the Keypad
1. Press [Off] to stop the motor before uploading or
downloading data.
2. Go to K-50 Keypad Copy.
3. Press [OK].
4. Select All from keypad.
5. Press [OK]. A progress bar shows the
downloading process.
6. Press [Hand] or [Auto] to return to normal
operation.
4.3 Restoring Default Settings
CAUTION
Initialization restores the unit to factory default settings.
Any programming, motor data, localization, and
monitoring records will be lost. Uploading data to the
keypad provides a backup before initialization.
Restoring the adjustable frequency drive parameter
settings back to default values is done by initialization of
the adjustable frequency drive. Initialization can be
through H-03 Restore Factory Settings or manually.
•
Initialization using H-03 Restore Factory Settings
does not change adjustable frequency drive data
such as operating hours, serial communication
selections, personal menu settings, fault log,
alarm log, and other monitoring functions
•
Using H-03 Restore Factory Settings is generally
recommended.
•
Manual initialization erases all motor,
programming, localization, and monitoring data
and restores factory default settings.
4.3.1 Recommended Initialization
1. Press [Main Menu] twice to access parameters.
2. Scroll to H-03 Restore Factory Settings.
3. Press [OK].
4. Scroll to [2] Restore Factory Settings.
5. Press [OK].
6. Remove power to the unit and wait for the
display to turn off.
7. Apply power to the unit.
Default parameter settings are restored during start-up.
This may take slightly longer than normal.
8. Alarm 80 is displayed.
9. Press [Reset] to return to operation mode.
4.3.2 Manual Initialization
1. Remove power to the unit and wait for the
display to turn off.
2. Press and hold [Status], [Main Menu], and [OK] at
the same time and apply power to the unit.
Factory default parameter settings are restored during
startup. This may take slightly longer than normal.
Manual initialization does not the following adjustable
frequency drive information.
•
ID-00 Operating Hours
•
ID-03 Power Up's
•
ID-04 Over Temp's
•
ID-05 Over Volt's
User Interface
AF-650 GP
TM
Design and Installation Guide
4-4 DET-767A
4