EasyManuals Logo
Home>GE>Security System>Concord 4

GE Concord 4 Installation Manual

GE Concord 4
144 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #116 background imageLoading...
Page #116 background image
Chapter 4: Testing and troubleshooting
110 Concord 4 Installation Manual
Automation module issues
Module is not controlling or communicating with the panel and panel indicates a
“BUS FAILURE UNIT nn” where nn is the automation module bus unit number.
Check that the module is wired correctly to the panel terminals.
Verify the SuperBus module’s red LED is flashing continuously. If the LED is not
flashing, remove power and check wiring.
Check that the RS-232 cable is firmly connected to the automation module and
the automation device.
Verify the automation device is powered and turned on.
Module is not controlling or communicating with the panel and panel does not
indicate a bus failure.
Verify the automation module is learned into panel memory.

Table of Contents

Other manuals for GE Concord 4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Concord 4 and is the answer not in the manual?

GE Concord 4 Specifications

General IconGeneral
BrandGE
ModelConcord 4
CategorySecurity System
LanguageEnglish

Related product manuals