Chapter 5: Diagnostics, maintenance, and testing
188 EST iO64 and iO500 Technical Reference Manual
Recalibrate device
Recalibrate device is used to calibrate a detector after it has been
cleaned. The recalibrate command resets the environmental
compensation and dirtiness level immediately. The panel can also
calibrate the device once it recognizes that it has been cleaned, but
this takes considerably more time than using this command. Once a
detector has been cleaned, you can quickly recalibrate the detector
by using this command to see if the detector has been cleaned
properly. If the device is not cleaned, the device trouble will return
meaning that more cleaning is required. If the device is cleaned, the
corresponding device trouble will clear.
Test
Control
Program
Diagnostics
Enter Password
0000
Diagnostics
Fast Ground Check
Recalibrate Device
Flash Device LED
Recalibrate Device
Loop 01<>
To recalibrate a device:
1. Press the Menu button.
2. Choose Diagnostics.
3. Enter the level two password.
4. Choose Recalibrate Device.
5. Choose the loop the device is on.
Note: If your panel only has one loop, the loop selection screen
does not display. Go to the next step.
6. Choose the device (number) that you want to recalibrate.
7. Press Enter.
Recalibrate Device
Device 001
Device 001