Chapter 1: System operation
EST iO64 and iO500 Technical Reference Manual 15
Events with event messages
Event type LCD display Printer [1]
Alarm Active type reporting
Input smoke Alarm active SMK ACT
Input smoke verified Alarm active SMK ACT
Input heat Heat alarm HEAT ACT
Input heat rate of rise Heat alarm HEAT ACT
Input duct alarm Alarm active DUCT ACT
Input pull station Pull station alarm PULL ACT
Input water flow Water flow WFLW ACT
Input water flow retard Water flow WFLW ACT
Zone alarm Alarm active ALRM ACT
Zone water flow Alarm active ALRM ACT
Supervisory type reporting
Input duct alarm Supervisory DUCT ACT
Zone supervisory Supervisory SUPV ACT
Input supervisory latching Supervisory SUPV ACT
Input supervisory nonlatching Supervisory SUPV ACT
Monitor type reporting
Zone monitor Monitor MON ACT
Input monitor Monitor MON ACT
Prealarm reporting Pre-alarm PALM ACT
Alarm verify reporting Alarm verify ALMV ACT
Maintenance alert reporting Maint. alert MANT ACT
Trouble All devices Trouble TRBL ACT
Disable All devices Disable DSBL ACT
Test All devices Test TEST ACT
[1] See "Printout examples" below for an example of how events are printed.
Printout examples
Event information is printed each time an event takes place
provided a printer is connected to your system. The following is an
example of what the event information looks like on the printout
and a description of each piece of information printed for an event.