EasyManuals Logo
Home>GE>Control Panel>EST iO64

GE EST iO64 User Manual

GE EST iO64
284 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
Chapter 1: System operation
EST iO64 and iO500 Technical Reference Manual 47
Disabling/enabling the dialer and network
Disabling
The dialer and network CMS connection and panel/device NACs
configured as city tie can be disabled so that they do not transmit
events to the CMS. When you disable the CMS connection:
The Remote Disconnect LED lights
"Dialer Dsbl/Rem Disc" is displayed on the LCD display
The disabled points counter on the LCD display increments
The active points counter on the LCD display increments
Pending events in the CMS queue are purged
To disable the dialer and network card:
1. Press Remote Disconnect.
2. Enter your password (the minimum of a level one password is
required).
Enabling
If the dialer and network CMS connection were disabled, they must
be enabled to transmit events to the CMS. When you enable the
dialer and network CMS connection:
The Remote Disconnect LED turns off
The message "Dialer Dsbl/Rem Disc" on the LCD display
disappears
The disabled points counter on the LCD display decrements
The active points counter on the LCD display decrements
To enable the dialer and network card:
1. Press Remote Disconnect.
2. Enter your password (the minimum of a level one password is
required).