Chapter 3: Programming
134 EST iO64 and iO500 Technical Reference Manual
Annunciator class programming
The annunciators connected to your system must have their wiring
class (Class A or Class B) programmed.
Default: Class B
Panel Configuration
Panel NAC
Ann. Class A<>
Annunciator
To program annunciator class:
1. Access the panel configuration options menu. See "Panel
configuration options."
2. Choose Ann. Class.
3. Select either Class A or Class B.
4. Program other panel configuration options or choose Save if
you're finished.
5. Continue programming your system or press Menu to exit menu
mode.
Panel Configuration
Ann. Class A<>
Annunciator
Save