ADL500 • Quick installation guide - Specifications and connection 59
8.2.15 Asynchronous/Synchronous selection
• To switch from Asynchronous to Synchronous:
Menu CONFIG DRIVE, PAR 540 Control type
04.01
DRIVE MONITOR
04.02
DRIVE INFO
04.03
DRIVE CONFIG
04.04
ALARM CONFIG
x2
03 /18
PAR: 540
Control type
ASY SSC
Value: 0
03 /18
PAR: 540
Control type
ASY SSC
Value: 0
03 /18
PAR: 540
Control type
SYN FOC
Value: 2
Press E to reset the drive and restart in the new operating mode.
Note ! Important: the default parameters including the LIFT application are reloaded.
This can only be done with the drive disabled.
• To switch from Synchronous to Asynchronous:
Menu CONFIG DRIVE, PAR 540 Control type
04.01
DRIVE MONITOR
04.02
DRIVE INFO
04.03
DRIVE CONFIG
04.04
ALARM CONFIG
x2
03 /18
PAR: 540
Control type
SYN FOC
Value: 2
03 /18
PAR: 540
Control type
SYN FOC
Value: 2
03 /18
PAR: 540
Control type
ASY FOC
Value: 1
The example shows the selection (1) ASY FOC, other modes are available: (0) ASY SSC, (2) SYN FOC.
Press E to reset the drive and restart in the new operating mode.
Note ! Important: the default parameters including the LIFT application are reloaded.
This can only be done with the drive disabled.