819XX_MAN_GRM-H_11-2022_ENG_pag. 28
5.1.1.4. Analog input correction offset
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
oFS
Inputs Analog input
R/W
s.p. 0.0
The parameter sets the analog input correction offset. It can be used to recalibrate the analog input or
set a minimum power. Example, if oFS=10.0, when the 0..10V input is at 0V the power supplied will
be 10.0%, at 9V it will be 100.0%.
min...max: -99.9...99.9
5.1.1.5. Analog input signal digital low-pass filter
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
FLt
Inputs Analog input
R/W
s 0.1
The parameter sets the time of the low pass filter on the analog input signal.
min...max: 0.0 ...20.0 s
5.1.1.6. Fault Action Power
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
FA.P Controls R/W
% 0.0
The parameter sets the power to be supplied in the event of an analog input fault.
When a 4 ... 20 mA input is used and the current is less than 2 mA, the Err state is generated and the
power defined in FA.P is supplied.
min...max: 0.0...100.0 %
Status
5.1.1.7. Analog input value (process variable)
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
P. V.
Status
R - s.p. -
Analog input engineering value read (process variable).