819XX_MAN_GRM-H_11-2022_ENG_pag. 70
5.6.4.1. Enabling feedback mode
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
hd.6
Power Control R/W
■
- 0
The parameter sets enabling of the feedback mode.
Options:
5.6.4.2. Voltage feedback reference
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
riF.V
Power Control R/W
■
V 0.0
The parameter sets the voltage feedback reference.
min...max: 0.0 ...999.9 V
5.6.4.3. Current feedback reference
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
riF.A
Power Control R/W
■
A 0.0
The parameter sets the current feedback reference.
min...max: 0.0 ...999.9 A
5.6.4.4. Power feedback reference
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
riF.P
Power Control R/W
■
kW 0.00
The parameter sets the power feedback reference.
min...max: 0.00 ...150.00 kW
0 No feedback enabled
1 V2 (quadratic voltage feedback)
2 I2 (quadratic current feedback)
3 P (power feedback)
4 Z (impedance feedback)
5 V (linear voltage feedback)
6 I (linear current feedback)