Settings
5.1.3.1. Voltage reading correction offset
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
o.tV
Inputs VT line input
R/W
V 0.0
Voltage reading correction offset.
min...max: -99.9 ...99.9 V
5.1.3.2. Voltage reading low pass digital filter
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
F.tV
Inputs VT line input
R/W
s 2.0
Voltage reading digital filter.
min...max: 0.0 ...20.0 s
Status
5.1.3.3. Voltage reading scale minimum limit
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
L.tV
Inputs VT line input
R
V 0.0
Voltage reading scale minimum limit.
5.1.3.4. Voltage reading scale maximum limit
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
H.tV
Inputs VT line input
R
V (*)
Voltage reading scale maximum limit.
(*)
Model Default
480 V 560.0
600 V 690.0
5.1.3. Line voltage value