EasyManuals Logo
Home>gefran>Controller>GRM-H 15

gefran GRM-H 15 User Manual

gefran GRM-H 15
97 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
819XX_MAN_GRM-H_11-2022_ENG_pag. 57
5.5.1.7. Communication error mode
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
C.E.m
Controls R/W
- 0
Communication error mode
The communication error in GRM-H-x-x-AN-x-x-x-x-x-x-x models is activated in the absence of the
Modbus serial communication while in the GRM-H-x-x-I-x-x-x-x-x-x-x models in the absence of
IO-Link communication
Options:
(*) In GRM-H-x-x-I-x-x-x-x-x-x-x models, it is not copied to Man.P.
5.5.1.8. Communication error timeout
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
C.E.t
Controls R/W
s 0
Communication error timeout
min...max: 0 99 s
5.5.1.9. Communication error power
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
C.E.P
Controls R/W
% 0.0
Output power with communication error
Attention! by setting a value > 0.0, if communication is not established at PowerOn, the device
erogates the C.E.P power after the C.E.t period.
min...max: 0.0 100.0 %
0 Disabled
1 Power is forced to C.E.P.
2 The power is forced to C.E.P. and copied to Man.P (*)