5.2.2.2. Enable memory for Power Fault alarms
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
PF.m
Alarms PF alarms
R/W
- 0
Enable memory for Power Fault alarm: after the causes that triggered the PF alarms have
disappeared, the alarms remain on until reset by key, serial line or IO-Link.
Options:
5.2.2.3. SSR_SHORT update time
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
dG.t
Alarms PF Alarms
R/W
s 10
SSR_SHORT alarm update or wait (in seconds) for alarm activation.
min...max: 1 ...999 s
5.2.2.4. NO_VOLTAGE and NO_CURRENT alarm filter
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
dG.F
Alarms PF Alarms
R/W
s 10
Time filter for NO_VOLTAGE and NO_CURRENT alarms
Note: it is recommended to set a value not lower than the cycle time.
min...max: 0 ...99 s
0 Disabled
1 Enabled