5.6.2.4. Maximum RMS current at steady state
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
Fu.tA
Power Control R/W
A (*)
The parameter sets the maximum limit of the RMS current at steady state.
The default value depends on the size of the controller:
min...max: 0.0 ... 999.9 A
(*)
Model Default
15 A 15.0
25 A 25I A 25.0
30 A 30I A 30.0
40 A 40.0
50 A 50.0
60 A 60.0
75 A 75.0
90 A 90.0
120 A 120.0
5.6.3. Triggering delay settings (trigge-
ring delay)
Triggering delay is a function that inserts a trigger
delay on the first cycle with inductive loads in start
modes ZC and BF. The startup delay is expressed in
degrees and can be set in the dL.t parameter).
5.6.3.1. Enable triggering delay
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
dL.E
Power Control R/W
- 0
Enable triggering delay.
Options:
5.6.3.2. Triggering delay
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
dL.t
Power Control R/W
° 60
Triggering delay
min...max: 0 ... 90 °
0 Disabled
1 Enabled